山东电缆桥架的使用对于我们的整个建筑行业来说,都有着重要的作用和价值,对于增加项目的便利性等方面,都有很大的优势!那么下面就来了解下建筑桥架的支吊架、吊架的安装内容。
The use of cable bridge in Shandong Province plays an important role and value for our entire construction industry, and has great advantages in increasing the convenience of the project! Then let's understand the installation contents of the supports and hangers of the building bridge.
支架和吊架所使用的钢应该是直立的,并且没有明显的扭曲。下部材料长度偏差应在3mm以内,切口不能有卷边和毛刺。
The steel used for supports and hangers shall be upright and free from obvious distortion. The length deviation of the lower material shall be within 3mm, and the cut shall be free of curling and burr.
钢支架和吊架应焊接牢固,无明显变形,支架和铁件焊接前厚度大于4mm应打坡口,焊缝均匀平整,焊缝长度符合要求,不能有裂纹、咬边、气孔、凹陷、漏焊等缺陷。
The steel support and hanger shall be welded firmly without obvious deformation. Before welding, the support and iron parts shall be beveled with a thickness of more than 4mm. The weld shall be uniform and flat, and the weld length shall meet the requirements. There shall be no cracks, undercuts, pores, depressions, missing welds and other defects.
支架和吊架应安装牢固,保证水平和垂直,在有斜坡的建筑物上安装支架和吊架,其高度和角度应与建筑物的斜坡和角度一致。
The support and hanger shall be installed firmly to ensure horizontal and vertical. The support and hanger shall be installed on the building with slope, and its height and angle shall be consistent with the slope and angle of the building.
支架和吊架的规格一般不能小于扁钢30mm×3mm;角钢25mm×25mm×3mm。
The specification of support and hanger shall not be less than 30mm of flat steel × 3mm; Angle steel 25mm × 25mm × 3mm。
严禁用电气焊对钢结构或轻钢龙骨的任何部位进行切割。
It is forbidden to cut any part of steel structure or light steel keel by electric welding.
通用吊具应采用定型产品,应有各自独立的吊卡或支撑系统。
The general lifting appliance shall adopt the finalized product and shall have its own independent elevator or support system.
固定支点的间距一般不大于1.5~3米,室外立柱的跨度一般为6米。出入接线盒、箱柜、转角处、拐角处和变形缝的三端500mm以内及丁字节连接处应设置固定支撑点。非线段的支吊架配置应遵循以下原则。当桥架宽幅小于300mm时,应在支吊架的支吊架侧面与支吊架的直线段为300~600mm的直线段。当桥架宽度大于300mm时,除了满足以上要求外,在非直线段的中间还应增设支吊架。
The spacing of fixed fulcrums is generally not more than 1.5~3 meters, and the span of outdoor columns is generally 6 meters. Fixed support points shall be set within 500mm of the three ends of the junction box, box, cabinet, corner, deformation joint and T-joint. The following principles shall be followed for the support and hanger configuration of non-section. When the width of the bridge is less than 300 mm, the straight section between the side of the support and the hanger and the support and hanger shall be 300~600 mm. When the width of the bridge is greater than 300mm, in addition to meeting the above requirements, supports and hangers shall be added in the middle of the non-linear section.
That's all about Shandong cable bridge. I hope you can refer to us //www.comprepyme.com The content given above will be helpful in the future use and application process!